Delta VFD-L Series Instruction Sheet

Delta VFD-L Series Instruction Sheet

please check for the following after receiving the AC motor drive.

◎ Inspect the unit to insure it was not damaged during shipment.

Make sure that the part number indicated on the nameplate corresponds

with the part number of your order.

Nameplate Information: Example of 1HP230V

AC Drive Model

MODEL :VFD007L21A

Input Spec.

:1PH/9.7A 3PH/5.1A 200-240V 50-60Hz

Output Spec.

OUTPUT :3PH 0-240V 4.2A 1.6kVA 1HP

Output Freq. Range

Freq. Range:1.0~400Hz

007L21A0T610001

DELTA ELECTRONICS, INC.

MADE IN XXXXX

Model Explanation

VFD 007 L 21 A

A: standard

D: PNP Mode

B: with EMI

E: PNP Mode with EMI Filter

Input voltage

VFD-L series

Applicable motor capacity

Variable Frequency Drive

Serial Number Explanation

007L21A0 T 6 10 001

Production number

Production week

Production year 2006

T: Taoyuan W: Wujiang

Production factory

230V 1-PHASE 1HP (0.75kW)

If there is any nameplate information not corresponding to your purchase

order or any problem, please contact your distributor.

230V IPHASE

Do not connect AC power to output

terminals (U,V,W).

Do not inspect components until LEDs

are turned off for at least 1min.

Read the user manual before operation.

10V A V I M 0 M 1 M 2 M 3 G N D

Basic Wiring Diagram

Users must connect wiring according to the circuit diagram shown below.

Please follow all National and State wiring codes, when wiring the VFD-L.

Figure 1 for models of VFD-L series

VFD002L11A, VFD002L11B, VFD002L21A, VFD002L21B, VFD004L11A,

VFD004L11B, VFD004L21A, VFD004L21B, VFD007L21A, VFD007L21B, VFD015L23A

Main Circuit Power

Factory default settings

Forward/Stop

Multi-function indication

output contacts

Reverse/Stop

120VAC/28VDC 3A

Factory default:

Fault Indication

Multi-step 1

Common Signal

Power supply for Potentiometer

Communication

Main circuit (power)

+10V 10mA(MAX)

Master Freq. setting

Control circuit terminals

Analog voltage

Shielded leads

Analog current

NOTE: Do not plug in a Modem or telephone line to the RS-485 communication port,

permanent damage may result. Terminals 1 & 2 are the power source for the

optional copy keypad and should not be used while using RS-485

communication.

*If the AC Drive model is VFD002L11A/B, VFD004L11A/B, VFD002L21B, VFD004L21B

or VFD007L21B, please use power terminals R/L1 and S/L2.

*If the AC Drive model is VFD002L21A, VFD004L21A or VFD007L21A, 1-phase/3 phase

power may be used on R/L1, S/L2, T/L3. When VFD002L21A/VFD004L21A or

VFD007L21A use 1-phase power, please select any two of the three input terminals

R/L1, S/L2, T/L3.

*If the AC Drive model is VFD015L23A, single phase power is not allowed.

Figure 2 for models of VFD-L series

VFD004L21D, VFD004L21E, VFD007L21D, VFD007L21E

Main Circuit Power

Power supply

Factory default settings

+15V 30mA(MAX)

Multi-function indication

Forward/Stop

output contacts

Reverse/Stop

120VAC/28VDC 3A

Factory default:

Fault Indication

Multi-step 1

Communication

Main circuit (power)

Master Freq. setting

Power supply

Analog voltage

+15V 30mA(MAX)

Control circuit terminals

Shielded leads

Analog current

NOTE: Do not plug in a Modem or telephone line to the RS-485 communication port,

permanent damage may result. Terminals 1 & 2 are the power source for the

optional copy keypad and should not be used while using RS-485

communication.

*If the AC Drive model is VFD004L21E, VFD007L21E, please use power terminals

R/L1 and S/L2.

*If the AC Drive model is VFD004L21D, VFD007L21D, 1-phase/3 phase power may be

used on R/L1, S/L2, T/L3. When VFD004L21D/VFD007L21D use 1-phase power, please

select any two of the three input terminals R/L1, S/L2, T/L3.

Wiring for NPN mode and PNP mode

NPN Mode for models:

VFD002L11A, VFD002L11B, VFD002L21A,

PNP Mode for models:

VFD002L21B, VFD004L11A, VFD004L11B,

VFD004L21D, VFD004L21E, VFD007L21D, VFD007L21E

VFD004L21A, VFD004L21B, VFD007L21A,

VFD007L21B, VFD015L23A

Multi-step 1

Multi-step 1

Digital Signal Common

*Don't apply the mains voltage directly

to above terminals.

*Don't apply the mains voltage directly

to above terminals.

Main circuit wiring

AC line input terminals

Single phase models input from R/L1, S/L2

R/L1 S/L2 T/L3

LED display

Display key

Confirmation key

Motor capacity

and input power

The signal selection

for AVI to input

communication

U/T1 V/T2 W/T3

Motor connections U/T1, V/T2, W/T3

Control circuit wiring

Figure 3 for models: VFD002L11A, VFD002L11B, VFD002L21A, VFD002L21B, VFD004L11A,

VFD004L11B, VFD004L21A, VFD004L21B, VFD007L21A, VFD007L21B, VFD015L23A

Wire Gauge:22-24AWG, Torque: 4Kgf-cm

RA RC +10V AVI M0 M1 M2 M3 GND

Figure 4 for models: VFD004L21D, VFD004L21E, VFD007L21D, VFD007L21E

Wire Gauge:22-24AWG, Torque: 4Kgf-cm

RA RC +15V AVI M0 M1 M2 M3 GND

Wiring Notes: PLEASE READ PRIOR TO INSTALLATION.

Do not connect the AC input to any of the U/T1, V/T2, W/T3

terminals, as it will damage the AC drive..

Ensure all screws are tightened to the proper torque rating.

During installation, follow all national and local electrical, construction,

and safety codes for the country the drive is to be installed in.

Ensure the appropriate protective devices (circuit breaker or fuses) are

connected between the power supply and AC drive.

Make sure that the leads are connected correctly and the AC drive is

properly grounded. (Ground resistance should not exceed 0.1Ω.)

Use ground leads that comply with AWG/MCM standards and keep

them as short as possible.

Multiple VFD-L units can be installed in one location. All the units should

be grounded directly to a common ground terminal. The VFD-L ground

terminals may also be connected in parallel, as shown in the figure

below. Ensure there are no ground loops.

When the AC drive output terminals U/T1, V/T2, and W/T3 are

connected to the motor terminals U, V, and W, respectively, the motor

will rotate counterclockwise (as viewed from the shaft ends of the motor)

when a forward operation command is received. To reverse the

direction of motor rotation, switch over any of the two motor leads.

Make sure that the power is capable of supplying the correct voltage

and required current to the AC drive.

Do not attach or remove wiring when power is applied to the AC drive.

Do not monitor the signals on the circuit board while the AC drive is in

Route the power and control wires separately, or orthogonal to each

If a filter is required for reducing EMI (Electro-Magnetic Interference),

install it as close as possible to AC drive. EMI can also be reduced by

lowering the Carrier Frequency.

If the AC drive is installed in the place where a load reactor is needed,

install the filter close to U/T1, V/T2, W/T3 side of AC drive. Do not use a

Capacitor or L-C Filter (Inductance-Capacitance) or R-C Filter

(Resistance-Capacitance).

When using a general GFCI (Ground Fault Circuit Interrupter), select a

current sensor with sensitivity of 200mA or above, and not less than

0.1-second operation time to avoid nuisance tripping. For the specific

GFCI of the AC motor drive, please select a current sensor with

sensitivity of 30mA or above.

Summary of Parameters

Group 0: User Parameters

The parameter may be set during operation.

Identity code of drive

Rated current display

Parameter reset

d10: Reset Parameters to Factory Setting

0-03 Start-up display of AC

d0: F (Frequency command)

d1: H (output frequency)

d2: U (user-defined unit)

d3: A (output current)

0-04 User-defined Unit

d0: Display User-Defined Unit (u)

d1: Display Counter Value (C)

d2: Display Process Operation (1=tt)

(Display the current speed's step and the

rest time for this step speed)

d3: Display DC-BUS voltage (U)

d4: Display output voltage (E)

0-05 User-defined

coefficient K

Software version

Password input

configuration

Group 1: Basic Parameters

Maximum operation Freq.

Maximum setting Freq.

Maximum output voltage

Mid-point freq.

Mid-point voltage

Minimum output freq.

Minimum output voltage

Upper bound of freq.

Lower bound of freq.

1-09 Accel time 1 (Tacc1)

1-10 Decel time 1 (Tdec1)

1-11 Accel time 2

1-12 Decel time 2

1-13 JOG Accel time

1-14 JOG Decel time

1-15 JOG frequency

Auto-accel/decel

S-curve setting in

acceleration

S-curve setting in

deceleration

Group 2: Operation Method Parameters

Source of frequency

d0: Digital keypad

d1: 0 ~ 10V from AVI

d2: 4 ~ 20mA from AVI

d3: Controlled by V.R on drive

d4: RS-485 communication interface

Source of operation

d0: By digital keypad

d1: By external terminals, keypad STOP

d2: By external terminals, keypad

d3: By RS-485 communication interface, keypad

d4: By RS-485 communication interface, keypad

Stop method

d0: Ramp stop d1: Coast stop

Carrier freq.

d3 ~d10K Hz

d50.0 ~ d400Hz

d10.0 ~ d400Hz

d2.0 ~ d255V

d1.0 ~ d400Hz

d2.0 ~ d255V

d1.0 ~ d60.0Hz

d2.0 ~ d255V

d0.1 ~ d600 Sec

d0.1 ~ d600 Sec

d0.1 ~ d600 Sec

d0.1 ~ d600 Sec

d0.1 ~ d600 Sec

d0.0 ~ d600 Sec

d1.0Hz~d400Hz

d0: Linear Accel/Decel

d1: Auto accel, linear decel

d2: Linear accel, auto decel,

d3: Auto Accel/Decel

d4: Linear accel. Auto decel, stall

prevention during

deceleration

d5: Auto accel. Auto decel, stall

prevention during

deceleration

STOP enable

STOP disable

Related Manuals for Delta VFD-L Series

Compact and panel-installation drives (88 pages)

Sensorless vector control compact drive (436 pages)

High performance/flexible options/micro tpe ac motor drives (396 pages)

General field oriented vector control drives (316 pages)

Vga splitter for two monitors (4 pages)

Multi-mode media converter ultimode (3 pages)

Single-mode media converter ultimode (4 pages)

12 mpx, 4k (3 pages)

For vfd-cmd 04/08 ac motor drives (2 pages)

Summary of Contents for Delta VFD-L Series